Performance of transmission lines 1
Question16
Question 12
A load of 1000 kw at 0.8 power factor lagging is received at the end of a 3 phase line 20 km long . The resistance and reactance of each conductor are 0.25 ohm and 0.28 ohm per kilometre.if the receiving end line voltage is maintained at 11 kv , calculate.
(1) Sending end voltage ( line to line )
(2) % regulation, (3) transmission efficiency ,
Solution =
Estimate the distance over which a load of 15000 kilowatt at 0.85 power factor can be delivered by a 3 phase transmission line having conductor of Steel cored Aluminium each of resistance 0.905 ohm per phase per kilometre. The voltage at the receiving end is to be 132 kv and the loss in transmission is to 7.5 % of the load .
Question 14
A 3 phase line 3 km long delivers 3000 kw at 0.8 lagging to a load . The resistance and reactance per km of each conductor are 0.4 ohm and 0.3 ohm respectively. If the voltage at the supply end is maintained at 11 kv , calculate. (1) Receiving end voltage ( line to line) (2) line current , (3) transmission efficiency ,
Solution =
Question 15A short 3 phase transmission line with an impedance of ( 5 +j20) ohm per phase has sending end and receiving end voltage of 46.85 kv and 33 Kv respectively for some receiving end load at a power factor of 0.8 lagging,
Determine= (1) power out put , (2) sending end power factor .
Solution=
Question 9
A Three phase load of 2000 KVA , 0.8 power factor is supplied at 6.6 KV , 50 Hz by means of a 33 KV transmission line 20 km and 33/6.6 kilo volt step down transformer . the resistance and reactance of each conductor are 0.4 Ohm and 0.5 ohm per km respectively . the resistance and reactance of transformer primary are 7.5 ohm and 13.2 ohm , while those of secondary are 0.35 ohm and 0.65 ohm respectively , find the voltage necessary at the sending end of transmission line 6.6 Kv is maintained at the receiving end . determine also the sending end power factor and transmission efficiency .
Solution
Here , the voltage drop will be due to the impedance of transmission line and also due to the impidence of transformer .
resistance of each conductor = 20 × 0.4 = 8 ohm ,
Reactance of each conductor = 20 ×0.5 = 10 ohm ,
Let us the transformer the impedance of Transformers secondary to High tension side 33 KV side ,
Equivalent resistance of transformer referred to 33 Kv side primary resistance + 0.35 (33/6.6)² ,
Question 10
total impedance z =
A Three phase line 3 km long delivers 3 MW at 0.8 lagging to a load . The resistance and reactance per kilometer of each conductor are 0.4 Ohm and 0.3 Ohm respectively . if the voltage at the supply end is maintained at 11 KV , calculate 1 . receiving and voltage ( line to line ) , 2 . line current , 3 . transmission efficiency ?
Question 11
Question
A Three phase line 3 km long delivers 3 MW at 0.8 lagging to a load . The resistance and reactance per kilometer of each conductor are 0.4 Ohm and 0.3 Ohm respectively . if the voltage at the supply end is maintained at 11 KV , calculate 1 . receiving and voltage ( line to line ) , 2 . line current , 3 . transmission efficiency ?
Question 19
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Question
Comments
Post a Comment