Power station 8

 Question = At the end of a power distribution system , a certain feeder supplies three distribution transformers ,each one supplying a group of customer whose connected load are as under :

 • transformer no. 1 load 10 kw , demand factor 0.65 , diversity of groups 1.5 ,

transformer no. 2 load 12 kw , demand factor 0.6 , diversity of groups 3.5 ,

transformer no. 3 load 15 kw , demand factor 0.7 , diversity of groups 1.5 ,

If the diversity factor among the transformer is 1.3 , find the maximum load on the feeder ? 

Solution = Show a feeder supplying three distribution transformers . 


» formula = maximum demand or , load  on feeder = sum of maximum demand transformer 1 + transf 2 +trans 3  ÷ diversity factor , 

» So , maximum demand trans.. no. 1 = ( connected load of trans. 1 × demand factor ) ÷ diversity factor  , 

= ( 10 kW × 0.65 ) ÷ 1.5 , = 4.33 kw , 

» maximum demand of trans . 2 =  ( 12 kw × 0.7 ) ÷ 3.5 , = 2.057 kw , 

» maximum demand of trans.  3 = ( 15 kw × 0.7 ) ÷ 1.5 , = 7 kw , 

» maximum demand on the feeder = as the diversity factor among trans.  is  1.3 , 

» So , maximum demand on feeder = ( 4.33 + 2.057 + 7 ) ÷ 1.3 , = 10.3 kw , answer ✓ 


Comments

Popular posts from this blog

Polyphase circuit part 6

Specific resistance की calculation

Heating element की resistance और power निकालना,